Commissioning (RF models only) 
If the thermostat and the receiver have been supplied together in 
a combined pack, the units have been paired in the factory and no 
commissioning is required (RX1 only).
To tune the RX receiver to the frequency of the thermostat signal, follow 
steps 1-5 below. 
Step 1  TP5000-RF
  Reset the unit by pressing and 
holding -, +, V and Λ together 
until display goes blank.
Step 2  Press and hold V and +   
buttons for 3 seconds  (TP5000 
now transmits unique signal continuously for 5 minutes).
Step 3  RX1
  Press and hold buttons PROG 
and CH1 for 3 seconds until green 
light fl ashes once.
Step 4  RX2 (if applicable)
  Stat 1 - perform steps 1-3. 
  Stat 2 - wait 5 mins, perform steps 1-2 and then press 
PROG and CH2 on RX2.
  RX3  (if applicable) 
  Stat 1 - perform steps 1-3.
  Stat 2 - wait 5 mins, perform steps 1-2 and then press 
PROG and CH2 on RX3.
  Stat 3 - wait 5 mins, perform steps 1-2 and then press 
PROG and CH3 on RX3.
Step 5  TP5000-RF
 Press V or Λ  to select temperature - the unit will revert back 
to operating mode. 