EasyManuals Logo

Danfoss VLT 6000 Instruction Manual

Danfoss VLT 6000
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background image
7
VLT is a registered Danfoss trademark
Wiring and terminal tightening specifications
Terminal tightening and wire specifications for the VLT2800 and
VLT 6000 are defined in Table I.
Total wiring length to connect up to 10 VLT 6000 and VLT 2800
drives from the BACLink portal should not exceed 3,000 feet
(900m) at 9600 baud rate.
Table I. Control Wiring and Torque
Specifications
Mounting requirements
Mount the BACLink enclosure as required using the predrilled
mounting holes (see Figure 2). The unit weighs approximately
15.3 pounds (7 kg).
For BACLink portals ordered without an enclosure, mount the unit
in an enclosed panel using the mounting holes provided on the
BACLink portal backplate (refer back to Figure 1). Leave about 2
inches (5 centimeters) on each side for wiring access. In addition,
the BACLink portal requires 24 VAC input power.
BACLink portal is a Class 2 device (less
than 30VAC, 100VA maximum). Take
appropriate isolation measures when
mounting BACLink portal in control panels
where non-Class 2 devices (for example,
120VAC) or wiring are present.
WARNING
!
11.00
[279.4]
0.31
[7.9]
4 PLCS.
9.00
[228.6]
12.22
[310.4]
12.22
[310.4]
4.21
[107.0]
NOTE: Dimensions in inches [mm].
Figure 2. BACLink Enclosure Mounting Dimensions
Torque
Specification
Control Wiring 24 VAC Input Wiring
4.5 in-lbs (0.5 Nm) 18 – 24 AWG
(0.75mm
2
– 0.2mm
2
)
shielded twisted pair
22 AWG (0.3mm
2
)

Other manuals for Danfoss VLT 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 and is the answer not in the manual?

Danfoss VLT 6000 Specifications

General IconGeneral
CategoryController
Cooling methodForced air cooling
EnclosureIP20
Output frequency range0-500Hz
Protection featuresOvervoltage, Undervoltage, Short circuit
Communication optionsProfibus
Ambient temperature range-10°C to +40°C

Related product manuals