Table 18: Errors 77–83
Error
num‐
ber
Description LED indications
Reason Action LED1 LED2 LED3 LED4
77 Internal er-
ror: Fail-safe
data CRC
mismatch.
Reaction:
STO.
The CRC of
the safety op-
tion does not
match the
stored CRC
value on the
drive.
Configure the safety op-
tion with MCT 10 Safe
Plug-in or by CRC se-
lect/LCP copy
Status of LED1 and LED2 de-
pends on the safety unction
state assigned to DI1 and DI2.
If safe fieldbus is
enabled, the sta-
tus of LED3 de-
pends on the
safe fieldbus sta-
tus. Otherwise,
LED3 is off.
Red
con-
stant.
78 Internal er-
ror: S1 S2
Communica-
tion Chan-
nel.
Reaction:
STO.
Severe excep-
tional error
caused by the
program run
in the safety
option.
Perform 1 of the follow-
ing actions:
• Power cycle the
drive.
• Restart the safety
option via parame-
ter 42-90 Restart Safe
Option.
• If the problem per-
sists, contact Dan-
foss.
80 Internal er-
ror: No CAN
communica-
tion.
Reaction:
STO.
81 Internal er-
ror: Under-
voltage
Vuc1.
Reaction:
STO.
82 Internal er-
ror: Over-
voltage
Vuc1.
Reaction:
STO.
83 Internal er-
ror: Under-
voltage 24 V
IO.
Reaction:
STO.
Maintenance, Diagnostics, and
Troubleshooting
Installation Guide | VLT®Safety Option MCB 152
AN327351953089en-000101 / 130R0578| 63