5-40 Function Relay
Option: Function:
[42] Above ref, high Active when actual speed is above
the speed reference setting.
[45] Bus ctrl. Controls digital output/relay via bus.
The state of the output is set in
5-90 Digital & Relay Bus Control. The
output state is retained in the event
of a bus time-out.
[46] Bus control, timeout:
On
Controls output via bus. The state of
the output is set in 5-90 Digital &
Relay Bus Control. In the event of a
bus time-out, the output state is set
high (on).
[47] Bus control, timeout:
Off
Controls output via bus. The state of
the output is set in 5-90 Digital &
Relay Bus Control. In the event of a
bus time-out, the output state is set
low (off).
[56] Heat sink cleaning
warning, high
[60] Comparator 0
See parameter group 13-1* Smart
Logic Control. If Comparator 0 in SLC
is TRUE, the output goes high.
Otherwise, it goes low.
[61] Comparator 1
See parameter group 13-1* Smart
Logic Control. If Comparator 1 in SLC
is TRUE, the output goes high.
Otherwise, it goes low.
[62] Comparator 2
See parameter group 13-1* Smart
Logic Control. If Comparator 2 in SLC
is TRUE, the output goes high.
Otherwise, it goes low.
[63] Comparator 3
See parameter group 13-1* Smart
Logic Control. If Comparator 3 in SLC
is TRUE, the output goes high.
Otherwise, it goes low.
[64] Comparator 4
See parameter group 13-1* Smart
Logic Control. If Comparator 4 in SLC
is TRUE, the output goes high.
Otherwise, it goes low.
[65] Comparator 5
See parameter group 13-1* Smart
Logic Control. If Comparator 5 in SLC
is TRUE, the output goes high.
Otherwise, it goes low.
[70] Logic rule 0
See parameter group 13-4* Logic
Rules. If Logic Rule 0 in SLC is TRUE,
the output goes high. Otherwise, it
goes low.
[71] Logic rule 1
See parameter group 13-4* Logic
Rules. If Logic Rule 1 in SLC is TRUE,
5-40 Function Relay
Option: Function:
the output goes high. Otherwise, it
goes low.
[72] Logic rule 2
See parameter group 13-4* Logic
Rules. If Logic Rule 2 in SLC is TRUE,
the output goes high. Otherwise, it
goes low.
[73] Logic rule 3
See parameter group 13-4* Logic
Rules. If Logic Rule 3 in SLC is TRUE,
the output goes high. Otherwise, it
goes low.
[74] Logic rule 4
See parameter group 13-4* Logic
Rules. If Logic Rule 4 in SLC is TRUE,
the output goes high. Otherwise, it
goes low.
[75] Logic rule 5
See parameter group 13-4* Logic
Rules. If Logic Rule 5 in SLC is TRUE,
the output goes high. Otherwise, it
goes low.
[80] SL digital output A
See 13-52 SL Controller Action.
Output A is low on [32] Smart Logic
Action. Output A is high on [38]
Smart Logic Action.
[81] SL digital output B
See 13-52 SL Controller Action.
Output B is low on [32] Smart Logic
Action. Output B is high on [38]
Smart Logic Action.
[82] SL digital output C
See 13-52 SL Controller Action.
Output C is low on [32] Smart Logic
Action. Output C is high on [38]
Smart Logic Action.
[83] SL digital output D
See 13-52 SL Controller Action.
Output D is low on [32] Smart Logic
Action. Output D is high on [38]
Smart Logic Action.
[160] No alarm
[161] Running reverse
[165] Local ref active
[166] Remote ref active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[170] Homing Completed
[171] Target Position
Reached
[172] Position Control
Fault
[173] Position Mech Brake
[175] Running on tension
[176] Ready to run
[193] Sleep Mode
[194] Broken Belt Function
Positioning Control
VLT
®
AutomationDrive FC 360