380–480 V/380–500 V units 525–690 V units
Inrush Circuit Enabled [V DC] 370 550
Inrush Circuit Disabled [V DC] 395 570
Inverter Undervoltage Disable [V DC] 373 553
Undervoltage Warning [V DC] 410 585
Inverter Undervoltage Re-enable
(warning reset) [V DC]
413 602
380–480 V units 380–500 V units
Overvoltage Warning (without brake) [V DC] 778 817 1084
Dynamic Brake Turn On [V DC] 778 810 1099
Inverter Overvoltage Re-Enable (warning reset)
[V DC]
786 821 1099
Overvoltage Warning (with brake) [V DC] 810 828 1109
Overvoltage Trip [V DC] 820 855 1130
Table 1.19 DC Voltage Levels