2.1.14 Initialization to Default Settings
Initialize the adjustable frequency drive to default settings in two ways:
Recommended initialization (via par.14-22
Operation Mode
)
1. Select par.14-22
Operation Mode
2. Press [OK].
3. Select “Initialization”
4. Press [OK].
5. Cut off the line power supply and wait until the display turns off.
6. Reconnect the line power supply - the adjustable frequency
drive is now reset.
7. Change par.14-22
Operation Mode
back to
Normal Operation
.
NOTE!
Resets parameters selected in Personal Menu with default factory setting.
par.14-22
Operation Mode
initializes all except:
par.14-50
RFI 1
par.8-30
Protocol
par.8-31
Address
par.8-32
Baud Rate
par.8-35
Minimum Response Delay
par.8-36
Max Response Delay
par.8-37
Max Inter-Char Delay
par.15-00
Operating Hours
to par.15-05
Over Volts
par.15-20
Historic Log: Event
to par.15-22
Historic Log: Time
par.15-30
Alarm Log: Error Code
to par.15-32
Alarm Log: Time
Manual initialization
1. Disconnect from line power and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while powering up for LCP 102, Graphical Display
2b. Press [Menu] while powering up for LCP 101, Numerical Display
3. Release the keys after 5 s.
4. The adjustable frequency drive is now programmed according to default settings.
This procedure initializes all except: par.15-00
Operating Hours
; par.15-03
Power-ups
; par.15-04
Over Temps
; par.15-05
Over Volts
.
NOTE!
When you carry out manual initialization, you also reset serial communication, par.14-50
RFI 1
and fault log settings.
Removes parameters selected in par.25-00
Cascade Controller
.
NOTE!
After initialization and power cycling, the display will not show any information until after a couple of minutes.
VLT
®
HVAC Drive Programming Guide 2 How to Program
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
2-19
2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55