2.1.14 Initialization to Default Settings
Initialize the adjustable frequency drive to default settings in two ways:
Recommended initialization (via par.14-22
Operation Mode
)
1. Select par.14-22
Operation Mode
2. Press [OK].
3. Select “Initialization”
4. Press [OK].
5. Cut off the line power supply and wait until the display turns off.
6. Reconnect the line power supply - the adjustable frequency
drive is now reset.
7. Change par.14-22
Operation Mode
back to
Normal Operation
.
NOTE!
Resets parameters selected in Personal Menu with default factory setting.
par.14-22
Operation Mode
initializes all except:
par.14-50
RFI 1
par.8-30
Protocol
par.8-31
Address
par.8-32
Baud Rate
par.8-35
Minimum Response Delay
par.8-36
Max Response Delay
par.8-37
Max Inter-Char Delay
par.15-00
Operating Hours
to par.15-05
Over Volts
par.15-20
Historic Log: Event
to par.15-22
Historic Log: Time
par.15-30
Alarm Log: Error Code
to par.15-32
Alarm Log: Time
Manual initialization
1. Disconnect from line power and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while powering up for LCP 102, Graphical Display
2b. Press [Menu] while powering up for LCP 101, Numerical Display
3. Release the keys after 5 s.
4. The adjustable frequency drive is now programmed according to default settings.
This procedure initializes all except: par.15-00
Operating Hours
; par.15-03
Power-ups
; par.15-04
Over Temps
; par.15-05
Over Volts
.
NOTE!
When you carry out manual initialization, you also reset serial communication, par.14-50
RFI 1
and fault log settings.
Removes parameters selected in par.25-00
Cascade Controller
.
NOTE!
After initialization and power cycling, the display will not show any information until after a couple of minutes.
VLT
®
HVAC Drive Programming Guide 2 How to Program
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
2-19
2