1.2.5 Disposal Instruction
Equipment containing electrical components must not be disposed of together with do-
mestic waste.
It must be separately collected with electrical and electronic waste according to local and
currently valid legislation.
1.3 Installation
1.3.1 Before Commencing Repair Work
1. Disconnect FC 51 from mains (and external DC supply, if present.)
2. Wait for 4 minutes (M1, M2 and M3) and 15 minutes (M4 and M5) for discharge of the DC-link.
3. Disconnect DC bus terminals and brake terminals (if present)
4. Remove motor cable
1.3.2 Side-by-Side Installation
The frequency converter can be mounted side-by-side for IP 20 rating units and requires 100 mm clearance above and
below for cooling. Please refer to the specifications near the end of this document for details on environmental ratings
of the frequency converter.
1.3.3 Mechanical Dimensions
A template for drilling can be found on the flap of the packaging.
Illustration 1.1: Mechanical dimensions.
Power (kW) Height (mm) Width (mm)
Depth
1)
(mm)
Max. Weight
Frame 1 X 200-240 V 3 X 200 -240 V 3 X 380-480 V A
A (incl. decoupling
plate)
a B b C Kg
M1 0.18 - 0.75 0.25 - 0.75 0.37 - 0.75 150 205 140.4 70 55 148 1.1
M2 1.5 1.5 1.5 - 2.2 176 230 166.4 75 59 168 1.6
M3 2.2 2.2 -3.7 3.0 - 7.5 239 294 226 90 69 194 3.0
M4 11.0-15.0 292 347.5 272.4 125 97 241 6.0
M5 18.5-22.0 335 387.5 315 165 140 248 9.5
1)
For LCP with potentiometer, please add 7.6 mm.
Table 1.1: Mechanical Dimensions