1.3.6 Connecting to Mains and Motor
The frequency converter is designed to operate all standard three-phased asynchronous motors.
The frequency converter is designed to accept mains/motor cables with a maximum cross-section of 4 mm
2
/10 AWG
(M1, M2 and M3) and maximum cross-section 16 mm
2
/6 AWG (M4 and M5).
Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to
both the decoupling plate and the motor metal.
Keep motor cable as short as possible to reduce the noise level and leakage currents.
For further details on mounting of the decoupling plate, please see instruction MI.02.BX.YY.
Also see EMC-Correct Installation in Operating Instruction MG.02.AX.YY.
Step 1: First, mount the earth wires to earth terminal.
Step 2: Connect motor to terminals U, V and W.
Step 3: Mount mains supply to terminals L1/L, L2 and
L3/N (3-phase) or L1/L and L3/N (single-phase) and
tighten.
Illustration 1.2: Mounting of earth cable, mains and motor
wires.
1.3.7 Control Terminals
All control cable terminals are located underneath the
terminal cover in front of the frequency converter. Re-
move the terminal cover using a screwdriver.
See back of terminal cover for outlines of
control terminals and switches.
Do not operate switches with power on the
frequency converter.
Parameter 6-19 must be set according to
Switch 4 position.
Illustration 1.3: Removing terminal cover.
Switch 1: *OFF = PNP terminals 29
ON = NPN terminals 29
Switch 2: *OFF = PNP terminal 18, 19, 27 and 33
ON = NPN terminal 18, 19, 27 and 33
Switch 3: No function
Switch 4: *OFF = Terminal 53 0 - 10 V
ON = Terminal 53 0/4 - 20 mA
* = default setting
Table 1.4: Settings for S200 Switches 1-4
Illustration 1.4: S200 Switches 1-4.