Fault
number
Alarm/
Warning
Bit
Number Fault text Warning Alarm
Trip
locked Cause of problem
54
AMA small
mot X The motor is too small for the AMA to be carried out.
55
AMA par.
range X
The parameter values found from the motor are outside
acceptable range.
56
AMA user
interrupt X The AMA has been interrupted by the user.
57 AMA timeout X
Try to start the AMA again a number of times, until the AMA is
carried out.
NOTE
Repeated runs may heat the motor to a level where the
resistance Rs and Rr are increased. In most cases, however,
this is not critical.
58 AMA internal X X Contact your local Danfoss supplier.
59 25 Current limit X The current is higher than the value in 4-18 Current Limit.
60 44
External
Interlock X
External interlock has been activated. To resume normal operation,
apply 24 V DC to the terminal programmed for external interlock
and reset the frequency converter (via serial communication,
digital I/O, or by pressing [Reset]).
66 26
Heat sink
Temperature
Low X
This warning is based on the temperature sensor in the IGBT
module (Only on 400 V 30-90 kW units).
69 1
Pwr. Card
Temp X X X
The temperature sensor on the power card is either too hot or too
cold.
79
Illegal power
section config-
uration X X Internal fault. Contact your local Danfoss supplier.
80 29
Drive
initialised X All parameter settings are initialized to default settings.
87 47
Auto DC
Braking X The frequency converter is auto DC braking.
95 40 Broken Belt X X
Torque is below the torque level set for no load, indicating a
broken belt. See parameter group 22-6* Broken Belt Detection.
200 Fire Mode X Fire mode has been activated
202
Fire Mode
Limits
Exceeded X Fire Mode has suppressed one or more warranty voiding alarms.
250 New sparepart X X
The power or switch mode power supply has been exchanged.
(Only on 400 V 30-90 kW units). Contact your local Danfoss
supplier.
251 New Typecode X X
The frequency converter has a new type code (only on 400 V,
30-90 kW units). Contact your local Danfoss supplier.
Table 1.22
Quick Guide
VLT
®
HVAC Basic Drive Cascade Controller Quick Guide
28 MG18F402 - VLT
®
is a registered Danfoss trademark
11

Other manuals for Danfoss VLT series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT series and is the answer not in the manual?

Danfoss VLT series Specifications

General IconGeneral
SeriesVLT
CategoryDC Drives
Output Voltage0-100% of input voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit, Ground Fault
Communication InterfacesProfibus, CANopen
Enclosure RatingIP20, IP21, IP55, IP66
Cooling MethodForced Air Cooling, Convection Cooling
Control ModeSensorless Vector, Closed Loop Vector
Ambient Temperature-10°C to +50°C (14°F to 122°F)