Service Guide
Preventative maintenance
Preventive maintenance has to be performed in order to:
Continue operation in specied range
Avoid malfunctions
Avoid inecient operation
Maximize the unit’s lifetime
The factory warranty is only valid if documented preventive maintenance has been
performed within time interval of:
Maximum 6 months when unit is located in normal air quality environment
Maximum 2 months when unit is located in bad quality air environment
A written log at site is adequate documentation for preventive maintenance.
Switch o power supply before working on the unit.
Make sure that all work has been performed correctly before switching power back on.
The unit must be cleaned according to the recommended preventive maintenance plan.
Tools required:
Vacuum cleaner or compressed air
Soft brush
TX20 screwdriver
AC cleaning agent if it is very dirty
Phase Description
1 Check and clean the outside air inlet grill. See page 8
2 Open the unit’s outer cover by removing the two screws in the lower edge of the
cover
3 Vacuum the condenser coil and the visible part of the fan
4 Vacuum the evaporator coil from the inside of the enclosure.
5 IF any of the coils are still dirty, please apply AC cleaning agent on coil ns, and
after 5 minutes, rinse gently with water WITHOUT spraying water on any electrical
parts.
6 Perform end inspection according to the list in next section.
Introduction
CAUTION
Cleaning
18