Network Variable Network Variable Type Description Units
1.3.6.1.4.1.22731.1.2.1.94.0 DisplayString
(SIZE (0..40))
Custom Alarm Message 3
Optional factory programmed
alarm message.
N/A
1.3.6.1.4.1.22731.1.2.1.95.0 DisplayString
(SIZE (0..25))
Custom Contact
Optional factory programmed
contact information.
N/A
1.3.6.1.4.1.22731.1.2.1.96.0 INTEGER (0..5)
Adjustment rate
Minutes
1.3.6.1.4.1.22731.1.2.1.97.0 INTEGER (0..900)
Optional Alarm 1 Delay
Seconds
1.3.6.1.4.1.22731.1.2.1.98.0 INTEGER (0..900)
Optional Alarm 2 Delay
Seconds
1.3.6.1.4.1.22731.1.2.1.99.0 INTEGER (0..900)
Optional Alarm 3 Delay
Seconds
1.3.6.1.4.1.22731.1.2.1.100.0 INTEGER
checkHumidCylinder(1)
customAlarm1(2)
fanMotorOverload(3)
humidLockout(4)
localAlarm(5)
heatAndHumidLockout(6)
heatLockout(7)
standbyPumpOn(8)
upsOn(9)
unitInStandby(10)
Optional Alarm 1
Configuration
N/A
1.3.6.1.4.1.22731.1.2.1.101.0 INTEGER
checkHumidCylinder(1)
customAlarm2(2)
fanMotorOverload(3)
humidLockout(4)
localAlarm(5)
heatAndHumidLockout(6)
heatLockout(7)
standbyPumpOn(8)
upsOn(9)
Optional Alarm 2
Configuration
N/A
1.3.6.1.4.1.22731.1.2.1.102.0 INTEGER
checkHumidCylinder(1)
customAlarm3(2)
fanMotorOverload(3)
humidLockout(4)
localAlarm(5)
heatAndHumidLockout(6)
heatLockout(7)
standbyPumpOn(8)
upsOn(9)
Optional Alarm 3
Configuration
N/A
1.3.6.1.4.1.22731.1.2.1.103.0 INTEGER
Humidity Sensor Calibration
0.1%RH
1.3.6.1.4.1.22731.1.2.1.104.0 INTEGER
Return Temperature Sensor
Calibration
0.1°F
1.3.6.1.4.1.22731.1.2.1.105.0 INTEGER
none(1)
pri(2)
pri-sec(3)
pri-pri(4)
pri-sec-pri-sec(5)
pri-pri-pri-pri(6)
Compressor Configuration
Factory setting
N/A
1.3.6.1.4.1.22731.1.2.1.106.0 INTEGER
off(1)
one-with-limits(2)
Dehumidifier Configuration
N/A
Document 600-000-615
11