90 ● gForce Ultra User Manual 10-2014
The following selections are available:
Comp Short Cycle:
Yes or No (Yes - factory setting)
Floor Water Alarm:
Alarm Only (factory setting)
Shutdown Unit
Lockout Comps
Reset Alarm Log:
Yes or No (No factory setting)
Alarm Screen Contact:
No Contact Message (factory setting)
Service Company
Maint Engineer
Data Proc Mngr
Custom Message (factory installed)
Once the selections have been made, with the cursor on the title line, Press the DOWN
key to advance to the next screen.
The following screen will be displayed (values are for reference only):
Press the ENTER key to move through the alarm/message inputs.
Press the UP or DOWN keys to change the alarm/message.
The following selections are available:
No Water Flow Action:
Turn Compressors Off
Alarm Only (factory setting)
Wtr Flow Alm Dly:
5 to 190 seconds (5 - factory setting)
Air Flow Alm Dly:
5 to 180 seconds (5 factory setting)