33 • Mini dap4 User Manual
The following will be displayed (values are for reference only):
Available Selections for Alarm #3:
SEE TAG INSIDE DOOR CUSTOM MESSAGE FAN MOTOR OVERLOAD
CHK HUMIDIFIER CYL STANDBY PUMP ON UPS ON-CHK MAIN POWER
P2 ON – CHK PRI PUMP REHEAT & HUM INHIBIT HUMIDIFIER INHIBITED
REHEAT INHIBITED
Once a selection or selections have been made, move the cursor to the title block (Alarm Inputs) by pressing the
ENTER key
▼ Press the DOWN key to view the next screen.
The following will be displayed (values are for reference only):
Note: If YES is selected, the alarm relay will energize. When the alarm is detected. If NO is selected, the alarm
relay will not energize when an alarm is detected.
Once a selection or selections have been made, move the cursor to the title block (Alm Output Function 1) by press-
ing the ENTER key
▼ Press the DOWN key to view the next screen.
The following will be displayed (values are for reference only):
Once a selection or selections have been made, move the cursor to the title block by pressing the ENTER key
Alm Output Function 1
Humidity Sensor YES
Ret Air Sensor YES
Chill Water Sensor YES
Dish Air Sensor YES
Fan Overload YES
Smoke detector YES
Condensation Wtr YES
Alm Output Function 2
Fire Status YES
C1 Hi Pressure YES
C1 Low Pressure YES
C2 Hi Pressure YES
C2 Low Pressure YES
Short Cycle YES
Maint Sched Timer YES
Alm Output Function 3
Hi Humidity YES
Low Humidity YES
Humidifier YES
Disch Air Low Temp YES
Ret Air Low Temp YES
Ret Air Hi Temp YES
Override YES