DKG-119 User Manual V-27 (20.04.2012)
- 22 -
The unit is able to send SMS messages in fuel theft or fuelling conditions.
These SMS messages are sent without creating visible fault condition.
These features are enabled by setting the program parameter Engine Parameters > Fuel
Consumption / Hour to a value other than 0%.
The Fuel Consumption / Hour parameter should be set to a value clearly greater than the
maximum fuel consumption of the engine.
If the fuel level measured from the sender input is decreased more than this parameter in 1
hour period, then a FUEL THEFT sms message is sent to programmed telephone numbers.
If the fuel level measured from the sender input is increased more than this parameter in 1
hour period, then a FUELLING sms message is sent to programmed telephone numbers.
The unit offers possibility of updating the firmware in the field. The firmware is updated through
the logic level serial port using Rainbow or a special DOS program.
The unit will go to firmware download mode with a special command from the PC program. In
download mode, the display of the unit will show “DL-V1.00
During firmware update process, the progress is visible through a completion bar on the
screen.
The firmware update operation will take around 3 minutes.
After completion of the update a special command will set back the unit to normal operation
mode.
In engine control mode, the unit is supposed to control an engine without alternator.
The engine control mode is activated by a program parameter in the Controller
Configuration group.
When the Engine Control Mode is activated:
-the unit will not display genset AC parameters (volts, amps, kW and pf).
-genset voltage and frequency protections are disabled. However engine rpm protections will
be active.
It is strongly recommended to enter correct low and
high rpm limit values in order to enable engine speed
protection.
Daha önceki parametre derlerine geri dönüş
mkün dildir.
6.21 Engine Control Mode
A logic level to RS-232 converter is necessary
in order to connect the unit to modem.
6.20 Firmware Update
6.19 Fuel Theft / Fuelling Messages

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Datakom DKG-119 and is the answer not in the manual?

Datakom DKG-119 Specifications

General IconGeneral
BrandDatakom
ModelDKG-119
CategoryController
LanguageEnglish

Related product manuals