DATAKOM DKG-705 User’s Manual
705_USER.doc - 15 -
4.2 Load Dump Alarms
Definition Source Description
Low Oil Press.Switch Digital Input
High Eng.Temp.Switch Digital Input
Emergency Stop Digital Input
Low Coolant Level Digital Input
Alternator High Temp. Digital Input
High Oil Temp. Digital Input
Overload Digital Input
Low Fuel Level Digital Input
Battery Charger Fail Digital Input
Spare Alarm 7 Digital Input
Spare Alarm 6 Digital Input
Spare Alarm 5 Digital Input
Spare Alarm 4 Digital Input
Spare Alarm 3 Digital Input
Spare Alarm 2 Digital Input
Spare Alarm 1 Digital Input
These load dump alarms are set depending on the digital input
settings. The related program parameters are P_700 to P_776.
Gen Reverse Power Internal Set if the genset consumes active power (KW) from the mains and
this power goes over the Reverse Power Load Dump (P_618)
limit.
Gen Excess Power Internal Set if the genset power (KW) supplied to the load goes over the
Excess Power Load Dump (P_617) limit for Overcurrent / Excess
Power Timer (P_511).
Alternator Overcurrent Internal Set if at least one of the genset phase currents goes over the
Overcurrent Limit (P_510) for Overcurrent / Excess Power
Timer (P_511).