DATAKOM DKG-705 User’s Manual
705_USER.doc - 3 -
1. INSTALLATION
1.1 Introduction to the Control Panel
The DKG-705 is a control and protection unit used in gensets. The 4 lines by 20 characters LCD
display allows the visualization of many measured parameters. The unit is designed to provide user
friendliness for both the installer and the user. Programming is usually unnecessary, as the factory settings
have been carefully selected to fit most applications. However programmable parameters allow the
complete control over the generating set. Programmed parameters are stored in a Non Volatile Memory
and thus all information is retained even in the event of complete loss of power.
The measurable parameters are:
Mains voltage phase R to neutral
Mains voltage phase S to neutral
Mains voltage phase T to neutral
Mains voltage phase R-S
Mains voltage phase S-T
Mains voltage phase T-R
Mains current phase R (optional)
Mains current phase S (optional)
Mains current phase T (optional)
Mains frequency
Mains KW phase R (optional)
Mains KW phase S (optional)
Mains KW phase T (optional)
Mains KVA phase R (optional)
Mains KVA phase S (optional)
Mains KVA phase T (optional)
Mains KVAr phase R (optional)
Mains KVAr phase S (optional)
Mains KVAr phase T (optional)
Mains cosΦ phase R (optional)
Mains cosΦ phase S (optional)
Mains cosΦ phase T (optional)
Mains total KW (optional)
Mains total KVA (optional)
Mains total KVAr (optional)
Mains total cosΦ (optional)
Gen voltage phase U to neutral
Gen voltage phase V to neutral
Gen voltage phase W to neutral
Gen voltage phase U-V
Gen voltage phase V-W
Gen voltage phase W-U
Gen current phase U
Gen current phase V
Gen current phase W
Gen frequency
Gen KW phase U
Gen KW phase V
Gen KW phase W
Gen KVA phase U
Gen KVA phase V
Gen KVA phase W
Gen KVAr phase U
Gen KVAr phase V
Gen KVAr phase W
Gen cosΦ phase U
Gen cosΦ phase V
Gen cosΦ phase W
Gen total KW
Gen total KVA
Gen total KVAr
Gen total cosΦ
Synchronoscope phase angle
Voltage match U-R
Battery voltage,
Engine RPM
Coolant temperature
Oil pressure
Oil temperature
Fuel level