DATAKOM DKG-705 User’s Manual
705_USER.doc - 57 -
Synchronization failure:
Check the parameters P_A02, P_A04, P_A15 and P_A16. If Dual Genset mode is used then check also
P_A39 and P_A40. If one of them is defined too low, this may delay or disable the synchronization
process.
Check the synchronization fail timeout parameter (P_A07), if necessary increase. A typical delay may be
20 seconds.
Check the synchronization limits (P_A10, P_A11, P_A12), If necessary widen the limits. A typical
application may be P_A10=0.5Hz, P_A11=5V, P_A12=5º
20. DECLARATION OF CONFORMITY
The unit conforms to the EU directives
-73/23/EEC and 93/68/EEC (low voltage)
-89/336/EEC, 92/31/EEC and 93/68/EEC (electro-magnetic compatibility)
Norms of reference:
EN 61010 (safety requirements)
EN 50081-2 (EMC requirements)
EN 50082-2 (EMC requirements)
The CE mark indicates that this product complies with the European requirements for safety, health
environmental and customer protection.