21. TECHNICAL SPECIFICATIONS
Alternator voltage: 0 to 300 V-AC (Ph-N)
Alternator frequency: 0-200 Hz.
Mains voltage: 0 to 300 V-AC (Ph-N)
Mains frequency: 0-200 Hz.
Current Measurement: from current transformers. ../5A. Max load 0.7 VA per phase.
Digital inputs: input voltage 0 to 35 V-DC. Internally connected to battery positive via 10 K-ohm resistors.
Analog Inputs: Resistor input 0 to 5000 ohms connected to battery negative. 10mA source current when
closed to battery negative.
Measurement Category: CAT II
Air Category: Pollution degree II
DC Supply Range:
12 V selection: 9.0 V-DC to 17.0 V-DC.
24 V selection: 18.0 V-DC to 30.0 V-DC.
Cranking dropouts: survives 0V for 100ms.
Current consumption: 500 mA-DC max. (Relay outputs open)
Total DC Current Output Rating: 10A-DC.
Max. Current for each Terminal: 10A-RMS.
Magnetic pickup voltage: 0.5 to 70Vpk.
Magnetic pickup frequency: 0 to 20000 Hz.
GOV Control Output: 0 – 10VDC
AVR Control Output: 300 ohms to 200 K-ohms adjustable, isolated.
Charge Alternator Excitation Current: Through resistor connected to FUEL output.
12 V selection: 36 mA-DC.
24 V selection: 72 mA-DC.
Communication Port: RS-232. 9600 bauds, no parity, 1 stop bit.
Operating temperature range: -20°C to 70°C (-4 to +158 °F).
Storage temperature range: -40°C to 80°C (-40 to +176°F).
Maximum humidity: 95% non-condensing.
IP Protection: IP65 from front panel, IP30 from the rear.
Dimensions: 192 x 144 x 49mm (WxHxD)
Mounting Opening Dimensions: 188 x 140mm minimum.
Weight: 800 g (approx.)
Case Material: High Temperature Self Extinguishing ABS (UL94-V0, 110°C)