DATAKOM DKG-705 User’s Manual
705_USER.doc - 40 -
Program Group 6
Group
Description
6 600
Reset Maintenance
Counters
- 0 1 Setting this parameter to 1 will
1) Reset the Time to Service
Maintenance Period (days) (P625) value,
2) Reset the Engine Hours to Service
variable to Maintenance Period (Engine
Hours) (P624) value.
This means that a new service period has
started with default values.
The program parameter P600 itself is not
modified and reads always 0.
6 601
Current Transformer
Primary
A 50 5000
This is the rated value of current
transformers. All transformers must have
the same rating. The secondary of the
transformer will be 5 Amps.
6 602
Low Oil Pr.
Shutdown
Bar 0 4.0 If the oil pressure measured from the
analog input falls below this limit while the
engine is running, this will generate a Low
Oil Pressure Measured alarm and shut
down the engine immediately.
6 603
Low Oil Pr. Warning Bar 0 4.0 If the oil pressure measured from the
analog input falls below this limit while the
engine is running, this will generate a Low
Oil Pressure Measured Warning.
6 604
High Temperature
Shutdown
°C
80 120 If the water temperature measured from the
analog input goes over this limit, this will
generate a High Coolant Temperature
Alarm and shut down the engine
immediately.
6 605
High Temp. Warning
°C
80 120 If the water temperature measured from the
analog input goes over this limit, this will
generate a High Coolant Temperature
Warning.
6 606
High Oil T. Shutdown
°C
80 250 If the oil temperature measured from the
analog input goes over this limit, this will
generate a High Oil Temperature Alarm
and shut down the engine immediately.
6 607
High Oil T. Warning
°C
80 250 If the oil temperature measured from the
analog input goes over this limit, this will
generate a High Oil Temperature
Warning.
6 608
Low Fuel Level
Shutdown
% 0 50 If the fuel level measured from the analog
input falls below this limit, this will generate
a Low Fuel Level Alarm and shut down
the engine immediately.
6 609
Low Fuel Level
Warning
%0 0 50 If the fuel level measured from the analog
input falls below this limit, this will generate
a Low Fuel Level Warning.