DATAKOM DKG-705 User’s Manual
705_USER.doc - 43 -
Group
Parameter
Definition Unit
Min Max
Description
6 629
Emergency Backup - 0 1 If this parameter is set to 1, in the TEST
mode, the load will be transferred to the
genset if the mains fail.
6 630
Frequency Voltage
Offset
V 5 50 This parameter adjusts the sensitivity for
genset frequency reading. If the genset
frequency appears to be a non-zero value
while the engine is at rest, increase this
parameter. The standard value is 20V.
6 631
Load Shedding Low
Limit
KW 0 5000
If the genset active power output goes
below this limit, then the Load Shedding
relay will be deactivated.
6 632
Load Shedding High
Limit
KW 0 5000
If the genset active power output goes
above this limit, then the Load Shedding
relay will be activated.
6 633
Mains Current
Transformers
- 0 1
0: Mains current transformers are not
connected. All mains current, power and
cosΦ values are zeros, peak lopping and
soft transfer to genset are not allowed
1: Mains current transformers are
connected and used. All mains current,
power and cosΦ measurements are valid,
peak lopping and soft transfer to genset
are allowed.
6 634
Modem Connection - 0 1
0: No modem connection, the serial port is
connected to PC
1: Modem connected.