Teach-in Parameters
Index
(dec)
Parameter
Object Name
Lenght
Subindex
(oset)
Value/Range Description Data Type Access* Remark
0x003A (58) TI Select 1 octet
0x00 = SSC1 (default, C/Q pin and DO
pin)
Selection for Teach-in channel (volatile) UIntegerT R/W
C/Q and DO outputs are antivalent.
Teach SSC1 equals to teach SSC2
0x003B (59) TI Result 1 octet
1(0)
2(4)
3(5)
Teach-in State
Flag SP1 TP1
Flag SP2 TP1
See IO-Link Smart Sensor Prole
UIntegerT4
BooleanT
BooleanT
RO
0x003C (60) SSC1 Param
2 octets
2 octets
1(16)
2(0)
280-1950
Not used
Switching threshold UIntegerT R/W Saved in non-volatile memory
0x003D (61) SSC1 Cong
1 octet
1 octet
1(24)
2(16)
0x00: High Active
0x01: Low Active (default)
0x01: Single Point (default)
C/Q pin conguration
UIntegerT
UIntegerT
R/W Saved in non-volatile memory
2 octets 3(0) 0 ..2 Hysteresis UIntegerT
0x003E (62) SSC2 Param
2 octets
2 octets
1(16)
2(0)
280-1950
Non used
Switching threshold UIntegerT R/W Saved in non-volatile memory
0x003F (63) SSC2 Cong
1 octet
1 octet
1(24)
2(16)
0x00: High Active (default)
0x01: Low Active
0x01: Single Point (default)
DO pin conguration
UIntegerT
UIntegerT
R/W Saved in non-volatile memory
2 octets 3(0) 0 ..2 Hysteresis UIntegerT
0x0040 (64)
Sensitivity
selection
1 octet 0 ..10 Sensitivity Sensitivity UIntegerT R/W Saved in non-volatile memory
Device Specic Parameters
Index
(dec)
Parameter
Object Name
Lenght
Subindex
(oset)
Value/Range Description Data Type Access* Remark
0x0048 (72) Delay Settings
1 octet 1(8)
0 = no delay (default)
0x4 = Delay OFF
Select Delay mode (OFF) UIntegerT R/W
Saved in non-volatile memory.
Max. Value 255 ms
*Available for future Beta samples
1 octet 2(0) 0...(2^8)-1 Delay value = Delay [ms] UIntegerT R/W
0x00B4 (180) Output type
1 octet
1 octet
1(8)
2(0)
0x01 = PNP (default)
0x03 = Push Pull
(1)
0x01 = PNP (default)
0x03 = Push Pull
0x04 = Input
Output type of C/Q pin when in SIO mode
Output type of DO pin
UIntegerT
UIntegerT
R/W
R/W
Saved in non-volatile memory
(1)
The No Output congured in Push Pull mode with an NPN load does not reactivate after a short circuit condition. Remove the short circuit condition and cycle power to the sensor.
*RO = read only, WO = write only, R/W = read/write