Table 4.5 Plug 5: Digital input
Terminal Text Function Technical data
39 In Configurable Negative switching only, < 100 Ω
40 In Configurable Negative switching only, < 100 Ω
41 In Configurable Negative switching only, < 100 Ω
42 In Configurable Negative switching only, < 100 Ω
43 In Configurable Negative switching only, < 100 Ω
44 In Configurable Negative switching only, < 100 Ω
45 In Configurable Negative switching only, < 100 Ω
46 In Configurable Negative switching only, < 100 Ω
47 MB on Configurable (application dependent) Negative switching only, < 100 Ω
48 MB off Configurable (application dependent) Negative switching only, < 100 Ω
49 GB/TB on
Configurable (application dependent),
also used for BTB ON
Negative switching only, < 100 Ω
50 GB/TB off
Configurable (application dependent),
also used for BTB OFF
Negative switching only, < 100 Ω
Table 4.6 Plug 6: Analogue output
Terminal Text Function Technical data
51 GOV (-) Voltage or PWM output Isolated
52 GOV (+) Voltage or PWM output Isolated
53 Not used - -
54 AVR (-) Voltage output Isolated
55 AVR (+) Voltage output Isolated
Table 4.7 Plug 7: AC current CT-side
Terminal Text Function Technical data
56 L1 (S1)
57 L2 (S1)
58 L3 (S1)
59 Com (S2) Common Must be connected to frame GND
60 L4 (S1) Neutral, Earth or Mains/Tie power
61 L4 (S2) Neutral, Earth or Mains/Tie power Must be connected to frame GND
Table 4.8 Plug 8: AC voltage measurement
Terminal Text Function Technical data
62 N A-side
63 L1 A-side
64 L2 A-side
65 L3 A-side