5.3.4 Power supply and start
1
2
3
4
5
6
7
DC (+)
DC (-)
Not used
Emerg. stop
Run coil
Crank
D+
Fuel
M
G
D+
B+
F1 F2
Fuses:
• F1: 2 A MCB, c-curve
• F2: 6 A MCB, c-curve
5.4 Communication
5.4.1 CAN bus power management system
19
20
21
22
23
24
25
26
27
28
29
30
31
32
PMS Hi
PMS Sh
PMS Lo
AGC 150 AGC 150 AGC 150
120120
PMS Hi
PMS Sh
PMS Lo
PMS Hi
PMS Sh
PMS Lo
Recommended cable: Belden 3105A or equivalent, 24 AWG (0.5 mm
2
) twisted pair, shielded, impedance 120 Ω, <40 mΩ/m, min. 95
% shield coverage.
INSTALLATION INSTRUCTIONS UK Page 21 of 22