MTR-3 Installation Instructions
DEIF A/S Page 16 of 51
M-Set user interface
Setting procedure
In order to modify instrument settings with M-Set, current parameters must be loaded first.
Instrument settings can be acquired via a communication link (serial or USB) or can be loaded
off-line from a file on a local disk. Settings are displayed in the M-Set setting window - the left part
displays a hierarchical tree structure of settings, the right part displays parameter values of the
chosen setting group.
General settings
General settings are essential for the transducer. They are divided into four additional sublevels
(Connection, Communication, Display and Security).
Description and location
Two parameters that are intended for easier recognition of a certain unit. They are especially used
for identification of the device or location on which measurements are performed.
Average interval
The averaging interval defines the refresh rate of measurements on communication and remote
display.
Temperature unit
Choose a unit for temperature display.
Maximum demand calculation (MD mode)
The instrument provides maximum demand values using thermal function. A thermal function
assures exponent thermal characteristic based on simulation of bimetal meters. Maximum values
and time of their occurrence are stored in the device. A time constant (t. c.) can be set from 1 to
255 minutes and is 6 times the thermal time constant (t. c. = 6 * thermal time constant).
You can download freeware M-Set from www.deif.com.