Chapter 7 Servo Parameters|ASDA-A&A+ Series 
7-28    
Revision April 2009 
•  D: Source of pulse command 
Setting 
value 
Input pulse interface 
Max. input pulse 
frequency 
Remark 
Line driver  500Kpps 
0 
Open collector  200Kpps 
CN1 Terminal Identification: 
PULSE, /PULSE, SIGN, /SIGN
1 
Line driver for  
high-speed pulse 
4Mpps 
CN1 Terminal Identification: 
HPULSE, /HPULSE, HSIGN, 
/HSIGN 
 
NOTE
 
1)  High-speed pulse function (max. input pulse frequency 4Mpps) is for ASDA-A+ only. 
 
P1 - 01● 
 
CTL  Control Mode and Output Direction  Communication Addr.: 0101H
Default: 00  Related Section: 
Applicable Control Mode: ALL  Section 6.1 
Unit: pulse (P mode), r/min (S mode), N-m (T mode)   
Range: 0 ~ 1110   
Settings: 
not used
A
B
C
 
•  A: Control mode settings 
•  B: Torque output direction settings 
Control mode settings: 
  Pt  Pr  S  T  Sz Tz
00  ▲  
01  ▲  
02    ▲  
03  ▲   
04  ▲  
05  ▲
06  ▲ ▲  
07  ▲   ▲   
08  ▲  ▲  
09  ▲ ▲   
10    ▲  ▲   
 
Torque output direction settings: 
  0  1 
Forward
 
Reverse
 
 