Chapter 8  MODBUS Communications|ASDA-A&A+ Series 
Revision April 2009     8-13 
RTU Mode:  
Command message:   Response message: 
ADR 01H  ADR 01H 
CMD 06H  CMD 06H 
02H (Upper bytes)    02H (Upper bytes) 
Starting data 
address 
00H (Lower bytes)   
Starting data 
address 
00H (Lower bytes) 
00H (Upper bytes)    00H (Upper bytes) 
Content of data 
64H (Lower bytes)   
Content of data 
64H (Lower bytes) 
CRC Check Low  89H (Lower bytes)    CRC Check Low  89H (Lower bytes) 
CRC Check High  99H (Upper bytes)    CRC Check High  99H (Upper bytes) 
LRC (ASCII Mode): 
LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the values of the bytes 
from ADR to last data character then calculating the hexadecimal representation of the 2’s-complement 
negation of the sum.  
For example, reading 1 word from address 0201H of the ASDA-A and ASDA-A+ series AC servo drive with 
address 01H.  
STX ‘:’ 
‘0’ 
ADR 
‘1’ 
‘0’ 
CMD 
‘3’ 
‘0’ 
‘2’ 
‘0’ 
Starting data address 
‘1’ 
‘0’ 
‘0’ 
‘0’ 
Number of data 
‘1’ 
‘F’ 
LRC Check 
‘8’ 
End 1  (0DH)(CR) 
End 0  (0AH)(LF) 
01H+03H+02H+01H+00H+01H = 08H, the 2’s complement negation of 08H is F8H. 
Hence, we can know that LRC CHK is ’F’,’8’. 
 
 
 