EasyManua.ls Logo

Delta Electronics VFD007M43B

Delta Electronics VFD007M43B
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Parameters|
4-38 Revision May 2008, ME14, SW V3.04
Settings Function Description
18 Counter Trigger Signal
Parameter value 18 programs Multi-Function Input Terminal:
M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)
to increase the AC drive
s internal counter. When an input is
received, the counter is increased by 1.
GND
18 counter
trigger signal
input.
Mx counter value increase by
1 when closed.
Trigger
Note: The Counter Trigger input can be connected to an
external Pulse Signal Generator when counting a
process step or unit of material. See the diagram
below.
2ms
2ms
Indication value
(Pr.64=1)
Counter trigger signal
Multi-function input terminal
Signal output with Pr.97
counter value is attained.
(Pr.97=3)
(Pr.45/46=13)
Signal output with Pr.96
counter value is attained.
(Pr.96=5)
(Pr.45/46=14)
The trigger timing
can't be less than
2ms.(<250Hz)
(Pr.38 to Pr.42 =18)
19 Counter Reset
Parameter value 19 programs Multi-Function Input Terminal:
M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)
to reset the counter.
GND
19 reset the
counter value.
Mx "close": reset counter.
Reset counter
20 No Function
Enter value (20) to disable any Multi-Function Input Terminal:
M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)
Note: Purpose of this function is to isolate unused Multi-
Function Input Terminals. Any unused terminals should
be programmed to 20 to insure they have no effect on
drive operation.

Related product manuals