QuiQ Charger Troubleshooting
46
CHARGE TIMEOUT
Flashes (Red):
Indicates the battery failed to charge within
the time allowed by the charge algorithm.
This could occur if the battery is of larger
capacity than the algorithm is intended for. In
unusual cases, it could mean charger output
is reduced due to high ambient temperature.
It can also occur if the battery is damaged,
old, or in poor condition.
•
Check the battery for damage such as
shorted cells and insufficient water. Try
the charger on a good battery.
•
Check for sufficient cooling air around
charger. If ambient temperature is over
35°C, consider using a fan to move air to
keep the charger cool.
•
If the same fault occurs on a good battery,
check the connections to the battery,
connections to the AC power source, and
AC voltage level.
•
Confirm that the nominal battery pack
voltage is the same as the battery charger
voltage.
•
If a charger displays this fault on a battery

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta-q QUIQ Series and is the answer not in the manual?

Delta-q QUIQ Series Specifications

General IconGeneral
Input Voltage85-265 VAC
IP RatingIP66
Input Frequency45-65 Hz
Storage Temperature-40°C to +85°C
Cooling MethodNatural Convection
Operating Temperature-20°C to 50°C
ProtectionOvertemperature
Agency ApprovalsUL, CE
CommunicationCAN bus