22
9. Technical specifications
Model
GES102R GES202R GES302R
Capacity
1KVA/700W 2KVA/1400W 3KVA/2100W
Rated Voltage 230V
Voltage Range
175V280V(Full Load)
80V~175V(100% to 50% Load de-rating Linearly)
Frequency
50Hz (±5.0 Hz)
Input
Power Factor
0.97
Voltage 230V
Frequency 50Hz
Voltage Regulation
±2%
Frequency Accuracy
±0.05 Hz
Wave Form Pure Sine Wave
Transient Response
+
8% (10%90% Linear Load)
THD
3%(Linear Load); 6%(Computer Load)
Overload Capacity
105%-125% for 3mins; 125%-150% for 30secs; >150%
for 1sec
Crest Factor 3:1
Output
Efficiency (AC-AC)
87%
Outlet Receptacle
IEC320×1×4 IEC320×2×4 + IEC320×1
Battery Voltage 36 V 72V 72V
Battery Type (Lead acid) 12V/ 7Ah 12V/ 9Ah
Back-up Time (Typical) 5mins (700W) 5mins (1400W)
5mins
(2100W)
Battery
Recharge Time
8 Hours After Complete
Discharge to Recover
80%
8 Hours After Complete
Discharge to Recover 90%
Transfer Time Transfer Time 4 ms
LED Status
On-lineBypassOn-batteryOverloadBattery Low
FaultBattery ReplaceBattery LevelLoad Level
LED
Alarm Buzzer
DB9 RS232
Interface
SNMP Slot Internal Internal
Standards EMC Approval EN50091-2 CLASS A
Noise (At 1 Meter) 46dBA 47dBA 55 dBA
Operating Temperature
0-40
Environment
Humidity 0%~90% (Non-Condensing)
Battery Start Yes
Extendable Battery Bank Yes
Others
Long Time Model Yes (Optional)
Dimension (W×D×H)
440x455x88.5 / mm
17.3 x 17.9 x 3.48/inch
440 x 455 x 88.5 / mm
17.3 x 17.9 x 3.48 / inch
Appearance
Weight Long Time 6.7 kg / 14.7 lb 9.2 kg / 20.2 lb
* All specifications are subject to change without prior notice.