100
Output
Setup Item Options Default
Output Phase
1-phase/ 3-phase 3-phase
Output Voltage
220V/ 230V/ 240V, 230V
Output Frequency
Auto
*
1
/
Converter-50 Hz
*
2
/
Converter-60 Hz
*
2
Auto
Output Sync. Freq. Range
± 0.5/ 1/ 3/ 5 Hz ± 3 Hz
Output Freq. Slew Rate
0.5/ 1/ 2/ 3/ 4 Hz/ Sec. 1 Hz/ sec.
Output Mode
Industrial/ IT Industrial
Standby Mode
Bypass Output/ No Output Bypass output
Overload Alarm
30% ~ 105% (5% per step) 105%
NOTE:
1.
*
1
When
Output Frequency
is set as ‘
Auto
’, the output frequency will vary according
to the bypass frequency.
If the bypass frequency is ≥ 55 Hz,
Free_ Run_ Frequency
/
Cold_ Start_ Frequency
will be set as 60 Hz.
If the bypass frequency is < 55 Hz,
Free_ Run_ Frequency
/
Cold_ Start_ Frequency
will be set as 50 Hz.
When
Output Frequency
is set as ‘
Auto
’ and
Standby Mode
is set as
‘
Bypass
Output
’, the bypass output range will be the same as
Output Sync. Freq. Range
.
2.
*
2
When
Output Frequency
is set as ‘
Converter-50Hz
/
Converter-60Hz
’, the UPS
will enter
Frequency Conversion
mode and the bypass output will be disabled.
Input
Setup Item Options Default
Bypass Max. Voltage
+ 10/ 15/ 20% + 15%
Bypass Min. Voltage
- 10/ 15/ 20/ 25/ 30/ 35/ 40% - 20%
Input Phase
1-phase/ 3-phase 3-phase