Amplon RT Series 101
ECO Mode
Setup Item Options Default
ECO Mode
Disable/ Enable Disable
ECO Max. Voltage*
1
5% ~ 15% (1% per step) +10%
ECO Min. Voltage*
1
5% ~ 15% (1% per step) +10%
NOTE:
*
1
The setup items
ECO Max. Voltage
and
ECO Min. Voltage
will only be shown on the
display when the UPS is in ECO mode.
Parallel
Setup Item Options Default
Redundant UPS
0 ~ 3 (1 per step) 0
ID
1 ~ 4 (1 per step) 1
Common Battery
Yes/ No No
On/ Off Settings
Setup Item Options Default
Energy Saving
Option 1: Enable/ Disable
Option 2: 1 min ~ 15 mins
(1 min per step)
Option 3: 600W ~ 3000W
(100W per step)
Disable
Sleep Mode
Option 1: Enable/ Disable
Option 2: 10 mins ~ 120 mins
(10 mins per step)
Disable
Auto Restart
Enable/ Disable Enable
Auto Start on AC
Enable/ Disable Disable