102
Battery
Setup Item Options Default
Automatic Battery Test
No Test/ Daily/ Weekly/
Bi-weekly/ Monthly
No Test
Deep Discharge Test
20% ~ 90% (10% per step) 90%
Low Battery Warning
Capacity
0% ~ 95% (5% per step) 10%
Warning of Remaining Time
0 min ~ 60 mins
(1 min per step)
2 mins
Runtime Limitation
Disable/ 1/ 2/ 3 …/ 240 mins
(1 min per step)
Disable
Charge Mode
2-stage/ 3-stage 2-stage
Internal Charging Current
1.5/ 2/ 3/ 4/ 5/ 6/ 7/ 8A 1.5A
External Battery Source
Standard Battery Pack/
Customer Own Batt. Pack
Standard Battery Pack
External Battery Type
Standard Battery Pack:
Lead-Acid Battery
Lithium-ion Battery
Customer Own Batt. Pack:
Lead-Acid Battery
Others
Lead-Acid Battery
(Standard Battery Pack -
Lead-Acid Battery)
Model Name
Quantity
Float Charging Voltage
EOD Voltage
Model Name: RT-10KB
Quantity: 1 ~ 999
Float Charging Voltage:
Auto (2.27 Vdc/ cell)
2.23 Vdc/cell ~ 2.3 Vdc/ cell
(0.01 Vdc/ cell per step)
EOD Voltage: 10.5 Vdc/ PC
Model Name:
RT-10KB
Float Charging
Voltage: Auto

Other manuals for Delta Amplon RT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Amplon RT Series and is the answer not in the manual?

Delta Amplon RT Series Specifications

General IconGeneral
BrandDelta
ModelAmplon RT Series
CategoryUPS
LanguageEnglish

Related product manuals