Amplon RT Series 103
Setup Item Options Default
(Standard Battery Pack –
Lithium-ion Battery)
Rated Voltage
Total Capacity
Float Charging Voltage
EOD Voltage
(displays automatically, no settable
items)
N/A
(Customer Own Batt. Pack -
Lead-Acid Battery)
Voltage/Qty
Total Capacity
Float Charging Voltage
EOD Voltage
Voltage/Qty:
144 Vdc/12 PCS, 192 Vdc/16 PCS,
204 Vdc/17 PCS, 216 Vdc/18 PCS,
228 Vdc/19 PCS, 240 Vdc/20 PCS,
252 Vdc/21 PCS, 264 Vdc/22 PCS
Total Capacity:
1 ~ 999 (Ah)
Float Charging Voltage:
Auto (2.27 Vdc/cell)
2.23 Vdc/cell ~ 2.3 Vdc/cell
(0.01 Vdc/cell per step)
EOD Voltage:
10.5 Vdc/PC ~ 11 Vdc/PC
(0.1 Vdc/PC per step)
Voltage/Qty:
240 Vdc/20 PCS
Float Charging
Voltage: Auto
EOD Voltage:
10.5 Vdc/PC
(Customer Own Batt. Pack -
Others)
Rated Voltage
Float Charging Voltage
EOD Voltage
Rated Voltage:
144 Vdc ~ 264 Vdc (1Vdc per step)
Float Charging Voltage:
150 Vdc ~ 310 Vdc (1V per step)
EOD Voltage:
114 Vdc ~ 242 Vdc (1V per step)
Rated Voltage:
240 Vdc
Float Charging
Voltage: 272 Vdc
EOD Voltage: 210 Vdc
Install date
YYYY/ MM/ DD