Amplon RT Series 117
Event
Code
Alarm
Message
Possible Cause Solution
0x8109
Over Heat
Shutdown - T
1. The vents are blocked.
2. The UPS has an internal
fault.
1. Check whether the vents are
blocked.
2. Contact service personnel.
0x8380
INV
Supervisor
Fault
The UPS has an internal
fault.
Please contact service personnel.
0x83C3
Output Relay
Fault - R
The INV output relay is
broken.
Please contact service personnel.
0x83C4
Output Relay
Fault - S
The INV output relay is
broken.
Please contact service personnel.
0x83C5
Output Relay
Fault - T
The INV output relay is
broken.
Please contact service personnel.
0x8581*
1
INV Over
Current
Shutdown - R
The UPS output phase L1
is short-circuited.
Check whether the output is short-
circuited.
0x8582*
1
INV Over
Current
Shutdown - S
The UPS output phase L2
is short-circuited.
Check whether the output is short-
circuited.
0x8583*
1
INV Over
Current
Shutdown - T
The UPS output phase L3
is short-circuited.
Check whether the output is short-
circuited.
0x8640
INV DC Offset
Fault
Shutdown
The INV output DC offset is
abnormal.
Please contact service personnel.
0xA001
Charger Fault
The UPS has an internal
fault.
Please contact service personnel.
0xA002
Charger Fault
The UPS has an internal
fault.
Please contact service personnel.
0xA080
Battery Fuse
Open
The battery fuses have
melted.
Please contact service personnel.