Amplon RT Series 13
3.2 Multi-function Buttons
No.
Multi-function
Button
Description
1
ON/ OFF
Button
The button has multiple functions. Please refer to the following for
detailed information.
1. Turn on
In standby/ bypass mode, press and hold the button for 3
seconds, and release it after you hear the beep sound. After
that, the UPS will start up.
Cold start: when there is no AC input, press and hold the button
for 3 seconds, and release it after you hear the beep sound.
After that, the UPS will run in battery mode. Please refer to
Chapter
9.1.2
for details.
2. Turn off
In online mode, press and hold the button for 3 seconds, and
release it after you hear the beep sound. After that, the inverter
will be off and the UPS will transfer to run in standby/ bypass
mode. The UPS will keep charging the batteries when in
standby/ bypass mode. To fully turn off the UPS, please
disconnect the UPS from the AC power.
In battery mode, press and hold the button for 3 seconds, and
release it after you hear the beep sound. After that, the UPS will
turn off its output.