20Amplon RT Gen3 Series
To allow shutdown, start-up and status monitoring for unattended UPS,
232 port and the other to the communication port of your PC. With the
monitoring software installed (http://datacenter-softwarecenter.deltaww.
com), you can schedule shutdown and start-up of the UPS and monitor
the UPS status via your PC.
The UPS is equipped with a Mini slot, where you can install the Mini
SNMP card (optional). After installation of the Mini SNMP card, advanced
communication and monitoring functions will be available.
please install the USB driver software in your computer after
connecting your computer to the UPS’s USB port. The software
can be downloaded from http://datacenter-softwarecenter.
deltaww.com.
5
Only applicable to models with P/N ending with 0BA
.
Keep pin 1 and pin 2 closed for UPS normal operation. To activate REPO
function, cut the wire between pin 1 and pin 2.
The REPO port can be connected to an external switch. After the external
switch is turned to the “OPEN” position, the UPS will switch off the
inverter immediately and cut off the UPS output without transferring to
the bypass mode.
The REPO port can also be used for ROO application, which allows
you remotely turn on/ off the inverter. If you need detailed ROO
information or ROO setup service, please contact your local dealer
or customer service
.