Chapter 8 ParametersASDA-A2R Series
Revision December, 2014
8-83
P2-05 SPR Switching Rate of Speed Loop Gain
Address: 020AH
020BH
Operational
Interface
Panel / Software Communication
Related Section: -
Default
100
Control
Mode
ALL
Unit
%
Range
10 ~ 500
Data Size
16bit
Format
DEC
Settings
Switch the changing rate of speed loop gain according to the gain
switching condition.
P2-06 KVI Speed Integral Compensation
Address: 020CH
020DH
Operational
Interface
Panel / Software Communication
Related Section:
6.3.6
Default
100
Control
Mode
ALL
Unit
rad/s
Range
0 ~ 1023
Data Size
16bit
Format
DEC
Settings
Increasing the value of speed integral compensation can enhance
speed response and diminish the deviation of speed control.
However, if the value is set too big, it would easily cause
resonance and noise.
P2-07 KVF Speed Feed Forward Gain
Address: 020EH
020FH
Operational
Interface
Panel / Software Communication
Related Section:
6.3.6
Default
0
Control
Mode
ALL
Unit
%
Range
0 ~ 100

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASD-A2R-0221 Series and is the answer not in the manual?

Delta ASD-A2R-0221 Series Specifications

General IconGeneral
BrandDelta
ModelASD-A2R-0221 Series
CategoryServo Drives
LanguageEnglish

Related product manuals