Chapter 7 Parameters  ASDA-B2 
7-88  Revision May, 2018 
P4-06 
▲■ 
 
FOT 
Digital Output Register (Readable and 
Writable) 
Address: 040CH 
040DH 
 
Operation 
Interface: 
Panel / Software  Communication 
Related Section:   
4.4.3 
 
Default: 0 
 
Control 
Mode: 
ALL 
 
Unit: - 
 
Range: 0 ~ 0x3F 
 
Data Size: 16-bit 
 
Format: Hexadecimal 
Settings: Contact control of the force output 
             0: Non-force output (When the communication sets to 0,  
it can cancel the force output function.) 
 
P4-07■ 
 
ITST  Input Status 
Address: 040EH 
040FH 
 
Operation 
Interface: 
Software (cannot 
read and write 
throught the panel) 
Communication 
Related Section:   
4.4.4, 8.2 
 
Default: 0 
 
Control 
Mode: 
ALL 
 
Unit: N/A 
 
Range: 0 ~ 01FF 
 
Data Size: 16-bit 
 
Format: Hexadecimal 
Settings: The DI input signal can come from external terminal (DI1 ~ DI9) or 
software SDI1 ~ 9 (Bit 0 ~ 8 of corresponding parameter P4-07) 
and is determined by P3-06. The corresponding bit of P3-06 is 1, 
which means the source is software SDI (P4-07). If the 
corresponding bit is 0, then the source is hardware DI. See the 
following graph: 
 
 
 
 
 
 
 
Read parameters: shows the DI status after combination 
Write parameters: writes the software SDI status 
For example: 
The value of reading P4-07 is 0x0011, which means DI1 and DI5 
is ON after combination. 
Internal 
SDI1~9 
(P4-07) 
External 
DI1~9 
DI after combination 
P3-06