DVP-ES3 Series Operation Manual
5-26
_5
Equation for current output Mode1:
( )
( )
×
+
×
=
32000
)(20
16000
mA
Offset
OffsetGainX
mAY
Y=
Current output, X=Digital input
Resolution:
0.625μA = 20mA/32,000
Equation for current input Mode2:
( )
( )
×
+
×
=
32000
)(20
6400
16000
640019200 mAX
mAY
Y=
Current output, X=Digital input
Resolution:
0.5μA = 16mA/32,000
Mode 0 of CR#2 ~ CR#5
-10V ~ +10V, Default: Gain = 16,000= , Offset = 0
Range of digital conversion
-32,000 ~ +32,000
Max./Min. range of digital
conversion
-32,768 ~ +32,767
Mode 0:
Digital input
10V
5V
-5V
+32000
-10V
-32000
+16000
0
Gain
Offset
Voltage
output
-32768
+32767
Mode 1 of CR#2 ~ CR#5
0mA ~ +20mA, Default: Gain = 16,000= , Offset = 0
Range of digital conversion
0 ~ +32,000
Max./Min. range of digital
conversion
0 ~ +32,767