EasyManuals Logo

Delta DVP-ES3 Series User Manual

Delta DVP-ES3 Series
411 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #138 background imageLoading...
Page #138 background image
DVP-ES3 Series Operation Manual
5-32
_5
Mode 4:
Current input
+32000
+16000
-16000
20mA
-32000
-20mA
10mA
0
Gain
Offset
Digital
output
+32384
-32384
Mode 5 of CR#2 ~ CR#5
0mA ~ +20mA, Default: Gain = 16,000= , Offset = 0
Mode 6 of CR#2 ~ CR#5
+4mA ~ +20mA, Default: Gain = 19,200 = ,
Offset = 6,400
=
Range of digital conversion
0 ~ +32,000
Max./Min. range of digital
conversion
-384 ~ +32,384
Mode 5:
Mode 6:
Current input
+32000
+16000
20mA
10mA
0
Gain
Offset
Digital
output
+32384
-384
Current input
+32000
+16000
20mA12mA
0
Gain
Offset
Digital
output
+32384
-384
4mA

Table of Contents