EasyManua.ls Logo

Delta DVPEN01-SL - Rtu

Delta DVPEN01-SL
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
26
receiving register
In data exchange, DVPEN01-SL will execute Write (Æ) first before Read (Å).
Quantity: A slave is able to send and receive at the same time maximum 100 consecutive data.
f For data exchange, D register is parted into 2 sections, D0000 ~ D4095 and D4096 ~ D9999.
Please DO NOT use different sections for the consecutive sent and received data (start
address + number of data).
5. See “Application Examples Section 6.11” for more details.
5.6 RTU
Use the “RTU” function to conduct mapping between Delta’s network modules DVPEN01-SL and
RTU-EN01.Set up the mapping information first, and you will be able to use WPLSoft in DVPEN01-SL to save
and retrieve the mapped bit (M) and register (D) in order to operate the remote RTU-EN01.
The settings
1. Enable Remote I/O Mapping:
Check the box to enable the remote I/O mapping. The mapping with remote RTU-EN01 will be
enabled according to the settings.
2. Communication Parameters:
Set up “Communication Timeout” (ms) and “Update Cycle” (ms) here.
3. PLC I/O Mapping:
Set up the start address of the mapped bit and analog register (RCR) of digital input (X) and
digital output (Y) on remoter RTU-EN01. The bit starts from M2000, and read/write register starts
from D2000/D3000. The software will automatically calculate the end address according to the
settings below.
4. Remote Device Mapping:
Check “Enable” and enter the remote RTU-EN01 ID (Slave ID), IP Address, number of digital
input points (RX), number of digital output points (RY), number of mapped read registers (Read)
and write register (Write).
DVPEN01-SL offers 4 slaves for mapping. Max. number of digital and analog points for mapping

Related product manuals