Ethernet Communication Module DVPEN01-SL 
DVP-PLC Operation Manual 
48 
6.9  Application of Data Exchange (2) 
        Available in firmware V2.0 and later versions 
Application 
“Always Enable” Data Exchange. Enable a timer and write the timer values into D0 ~ D99. 
Continue to write the present values in D0 ~ D99 of PLC_A into D0 ~ D99 of PLC_B, and 
write the values in D0 ~ D99 of PLC-B into D200 ~ D299 of PLC_A. 
Network 
requirement 
(1)  Adopting static IP. 
(2)    IP of PLC_A: 192.168.1.99 
(3)    IP of PLC_B: 192.168.1.97” 
(4)    Update from PLC_A to PLC_B and PLC_B to PLC_A. 
1.    See 6.1 for how to set up the communication. 
2.    Open the setup page of PLC_A and switch to “Data Exchange” page. 
 
4.  Check “Enable Data Exchange” box. Select “Always Enable” for Execute Mode. Enter IP address of 
PLC_B “192.168.1.97”, D200ÅD0 Quantity: 100 and D0ÆD0 Quantity: 100 in No. 1 Data Exchange 
Host IP column. Click “OK” to complete the setting. 
 
 
5.  After all the settings in PLC_A are completed, compile the ladder diagram in the MPU and download it 
to PLC_A. See below for the program design: