Chapter 8 Parameters ASDA-A2
8-126 Revision February, 2017
Settings
Special-bit Register 2:
B7 B6 B5 B4 B3 B2 B1 B0
- - - - - - - -
B0~B1: Reserved
B2: Cancel latch function of low-voltage error
0: Latch function of low-voltage error: the error will not be cleared
automatically.
1: Cancel latch function of low-voltage error: the error will be cleared
automatically.
B3: Reserved
B4: Cancel the detection of AL.044
0: AL.044 will occur
1: AL.044 will be ignored.
B5: Enable disconnection detection of linear scale (only when the full-
closed loop control function is enabled)
0: AL.041 will be ignored
1: AL.041 will occur
B6~B8: Reserved
B9: When AL.003 occurs, switch on DO.ALM or DO.WARN
0: When AL.003 occurs, switch on DO.WARN.
1: When AL.003 occurs, switch on DO.ALM
B10~B15: Reserved.
P2-67 JSL The Stable Level of Inertia Estimation
Address: 0286H
0287H
Operational
Interface
Panel / Software Communication
Related Section: -
Default
1.5 15
Control
Mode
ALL
Unit
1times 0.1times
Range
0 ~ 200.0 0 ~ 2000
Data Size
16-bit
Format
One decimal Decimal
Example
1.5 = 1.5 times 15 = 1.5 times
Settings
In semi-auto mode, if the value of inertia estimation is smaller than P2-
67 and the status remains for a while, the system will regard the inertia
estimation as completed.