enteliZONE Sequence of Operations
Page 62 of 84 eZV-440 Application Guide
Edition 2.6
Setpoints and Occupancy Modes
The occupancy modes determine which temperature setpoints are used for the space.
Occupied Mode
In occupied mode:
Current heating setpoint = Occupied heating setpoint + Occupied setpoint offset
Current cooling setpoint = Occupied cooling setpoint + Occupied setpoint offset
In occupied mode (with Eco Mode set up on network sensor or enabled using MV13 object):
Current heating setpoint = Occupied heating setpoint + Occupied setpoint offset - Eco Mode
Setback
Current cooling setpoint = Occupied cooling setpoint + Occupied setpoint offset + Eco Mode
Setback
Occupant setpoint sits between the occupied heating and cooling setpoints. The occupied setpoint
offset is restricted to be within the occupied setpoint offset range.
In Eco Mode, the occupied setpoint offset range is relaxes by the amount specified by the Eco
Mode Setback.
For night overrides, a pushbutton or motion override initiates the Night override mode.
Standby Mode
In standby mode:
Current heating setpoint = Occupied heating setpoint + Occupied setpoint offset - Standby
Setback
Current cooling setpoint = Occupied cooling setpoint + Occupied setpoint offset + Standby
Setback
In standby mode (with Eco Mode set up on network sensor or enabled using MV13 object):
Current heating setpoint = Occupied heating setpoint + Occupied setpoint offset - Eco Mode
Setback - Standby Setback
Current cooling setpoint = Occupied cooling setpoint + Occupied setpoint offset + Eco Mode
Setback + Standby Setback
Unoccupied Mode
In unoccupied mode:
Current heating setpoint = Unoccupied heating setpoint
Current cooling setpoint = Unoccupied cooling setpoint