Installation Manual
26
Wiring Instructions
Table 4: Grounding Wire Sizing and Ratings (Continued)
Cable Type
Solid Copper Conductor
Quantity
1
Communication and I/O Wire Sizing and Ratings
Here are the requirements for the communication and I/O wires:
Table 5: Communication and I/O Wire Sizing and Ratings
Cable Type
Solid Copper Conductor
Voltage Rating
600 Volts or greater
Temperature
90°C or greater
Gauge
1.32 mm
2
(16 AWG)
Quantity
Depending on customer needs
Preparation of Cables
This section describes how to prepare the corresponding cables and wires to meet the specified
requirements, see section “Wire Sizing and Ratings” on page 24.
2 x 1500V, 1/0 AWG cables for DC (battery) connection
6 x 600V or greater, 1/0 AWG ~ 2 AWG cables for AC connection
1 x 600V or greater, 1/0 AWG ~ 3 AWG cables for grounding
300V or greater, 16 AWG wires for communication or I/O connection.