Installation Manual
46
Appendix
Appendix
Specifications
Table 18: Technical Specifications of the Delta PCS100HV
Item
Description
Grid-tied Operation
Rated Grid Voltage
400 Vac (3P,N,PE) or (3P,PE)
Grid Voltage Range
310 ~ 450 Vac
Rated Grid Frequency
50 Hz
Frequency Range
45~55 Hz
Rated AC Power
100 kVA / kW
Rated AC Current
145 A
Max. Continuous AC Current
167 Arms
Current THD
< 3%
Power Factor
-1 to 1, continuously adjustable
Battery Input Performance
DC Voltage Range
650 ~ 1,350 Vdc for 3P3W 1)
700 ~ 1,350 Vdc for 3P4W in Off-grid mode 1), 2)
Rated DC Voltage
900 Vdc
Rated Discharge Power
102 kW
Rated Charge Power
98 kW
Max. Discharge DC Current
157A
Max. Charge DC Current
151A
Standalone Mode Performance
Rated Output Voltage
400 Vac (3P,N,PE)
Rated Output Power
100 kVA/kW with linear load;
80 kVA with RCD load (Ipk240A) 3)
Rated Output Current
145A
Rated Output Frequency
50 Hz ± 1%
Power Factor
0.8 to 1
Output Voltage Accuracy
1%
Voltage Symmetry
± 1%, @ 100% linear balanced load
Output Voltage THD
< 3% @ liner load
Environment
Max Altitude
4,000 m, de-rating >3000m
Operating Temperature
-30 ºC to +60 ºC, de-rating >45ºC
Storage Temperature
-30 ~ 70ºC
Humidity
0 to 95% RH, no-condensing
Cooling
Forced air with speed control
Pollution Degree
III
Acoustic Noise
< 70 dB @ 1 m @25ºC @ rated condition