The ID of PCS should be set according to the following table.
Table 15: ID setting of SWR4
Terminal resistor setting switches (SWR3, SWR5, SWS5)
The SWR3 and SWR5 switches are used to set the terminal resistors of RS485 and CAN for PCS parallel
communication. The SWS5 switches are used to set the terminal resistors of CAN for BMS
communication. When the switch is placed at the upper side (ON Marking), the corresponding terminal
resistor is connected.
Figure 34. SWR3, SWR5, SWS5 Assignment
EMS Communication wiring
The PCS100HV supports Ethernet for communication. Ethernet can be used for a site controller or EMS
or remote server.
A 120ohm terminal resistor must be set in the site controller before it’s connected.
The connection diagram of communication is shown in the following figure.