EasyManua.ls Logo

Delta VFD-ED Series

Delta VFD-ED Series
447 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12 Descriptions of Parameter Settings | VFD-ED
12-11-2
When Bit 7 = 1, zero speed position control is enabled (refer to Chapter 12 Parameter Group 02 Elevator
Timing Diagram). Pr.10-22 is valid only when bit 7 is set to 1, and this function only supports PM motors.
When Bit 9 = 1, valid only when Pr.10-00 is set to 3, and the mechanical brake must be in engaged status.
Elevator Speed
Control Mode
FOCPG FOCPM Default: 1.00
Settings 0.104.00 m/s
Traction Sheave Diameter
Control Mode
FOCPG FOCPM Default: 400
Settings 1002000 mm
Gear Ratio
Control Mode
FOCPG FOCPM Default: 1.00
Settings 1.00100.00
Suspension Ratio
Control Mode
FOCPG FOCPM Default: 1
Settings 0 = 1: 1
1 = 2: 1
2 = 4:1
3 = 8:1
Mechanical Inertial Ratio
Control Mode
FOCPG FOCPM Default: 40
Settings 1–300%
You can calculate the load inertia according to the settings of motor parameters, Pr.11-02 Traction
Sheave Diameter, Pr.11-14 Motor Current at Acceleration and Pr.11-15 Carriage Acceleration. You can
use this parameter to adjust the mechanical inertia ratio.
Mechanical inertia reference value (%):

Table of Contents

Related product manuals