EasyManua.ls Logo

Delta VFD-ED Series

Delta VFD-ED Series
447 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 13 Warning Codes | VFD-ED
13-3
ID
No.
Display on
KPED-LE01
Display on KPC-CC01 Descriptions
10
oH2
Capacitor overheat warning
Cause
The temperature of the capacitor is over 65˚C.
15

PGF1
PG feedback error
Cause
When Pr.10-03 = 0 (default = 2), a warning message
displays instead of a fault message when an error
occurs.
16

PGF2
PG feedback loss warning
Cause
Pr.10-03 = 0 (default = 2), a warning message
displays instead of a fault message when an error
occurs.
17

PGF3
PG feedback stall warning
Cause
Pr.10-09 = 0 (default = 2), a warning message
displays instead of a fault message when an error
occurs.
18

PGF4
PG slip error warning
Cause
Pr.10-09 = 0 (default = 2), a warning message
displays instead of a fault message when an error
occurs.
19
PHL
PHL
Phase Loss
Warning
Phase loss
Cause
When Pr.06-01 =0 (default = 2), a warning message
displays instead of a fault message when a phase
loss occurs.
20
ot1
ot1
Over Torque 1
Warning
Over-torque 1
Cause
When Pr.06-05 =1 or 3 (default = 0), a warning
message displays instead of a fault message when
there is an over-torque detection.
21
ot2
ot2
Over Torque 2
Warning
Over-torque 2
Cause
When Pr.06-05 =1 or 3 (default = 0), a warning
message displays instead of a fault message when
there is an over-torque detection.
22
oH3
Motor overheat (PTC)
Cause
When Pr.06-26 = 0 (default = 0), a warning message
displays when there is a PTC detection.
oH2
Capacitance oH
Warning
PGF1
Warning
PGF2
Warning
PGF3
Warning
PGF4
Warning
oH3
Motor Over Heat (PTC)
Warning

Table of Contents

Related product manuals