Chapter 4 Parameters
VFD-EL-W
4-95
When the pressure sensor is set to 10 kg, Pr.10.49=1 and Pr.10.12=10.0% (that is, the physical quantity=1
kg), and if the set point=3 kg and feedback < 1 kg, then the AC motor drive follows the setting for Pr.10.20.
10.50
Number of Times of Restart after PID Fault
Settings 0–1000 times Default: 0
When you set Pr.10.20 =4, this parameter sets the number of times to restart when PID error occurs.